Standard Tank Sizes
Vertical/Aboveground/Single Wall/U.L.
| CAPACITY (gals) | DIMENSIONS (dia x length) | GAUGE | APPROX WT (lbs) |
| 150 | 30" x 4'-0" | 12 ga shell, bottom, cone roof | 190 |
| 300 | 38" x 5'-0" | 12 ga shell, bottom, cone roof | 245 |
| 550 | 48" x 6'-0" | 12 ga shell, bottom, cone roof | 600 |
| 1,000 | 64" x 6'-0" | 10 ga shell, bottom, cone roof | 1180 |
| 1,500 | 64" x 9'-0" | 7 ga shell and cone roof, 1/4" bottom | 1560 |
| 2,000 | 64" x 12'-0" | 3/16" shell and cone roof, 1/4" bottom | 1980 |
| 2,500 | 64" x 15'-0" | 3/16" shell and cone roof, 1/4" bottom | 2370 |
| 3,000 | 72" x 14'-0" | 3/16" shell and cone roof, 1/4" bottom | 2565 |
| 4,000 | 96" x 11'-0" | 3/16" shell and cone roof, 1/4" bottom | 3150 |
| 5,000 | 96" x 13'-4" | 3/16" shell and cone roof, 1/4" bottom | 3800 |
| 6,000 | 96" x 16'-0" | 3/16" shell and cone roof, 1/4" bottom | 4300 |
| 8,000 | 96" x 21'-4" | 3/16" shell and cone roof, 1/4" bottom | 5350 |
| 8,000 | 120" x 14'-0" | 3/16" shell and cone roof, 1/4" bottom | 4900 |
| 10,000 | 10'-6" x 16'-0" | 3/16" shell and cone roof, 1/4" bottom | 5950 |
| 12,000 | 10'-6" x 18'-0" | 3/16" shell and cone roof, 1/4" bottom | 6670 |
| 15,000 | 10'-6" x 24'-0" | 3/16" shell and cone roof, 1/4" bottom | 8050 |
| 20,000 | 10'-6" x 31'-0" | 1/4" lower 7'-0" of shell, 3/16" remainder of shell and cone roof, 1/4" bottom | 10100 |
| 25,000 | 12'-0" x 30'-0" | 1/4" lower 6'-0" of shell, 3/16" remainder of shell and cone roof, 1/4" bottom | 12200 |
| 30,000 | 12'-0" x 35'-0" | 1/4" lower 11'-0" of shell, 3/16" remainder of shell and cone roof, 1/4" bottom | 14200 |
Vertical Aboveground/Double Wall/F921® & Flameshield®
| CAPACITY (gals) | DIMENSIONS (dia x length) | GAUGE | APPROX WT (lbs) |
| 300 | 38" x 5'-0" | 10 ga primary shell / 12 ga secondary shell 10 ga primary & secondary heads | 948 |
| 550 | 48" x 6'-0" | 10 ga primary shell / 12 ga secondary shell 10 ga primary & secondary heads | 975 |
| 1,000 | 64" x 6'-0" | 10 ga primary shell / 10 ga secondary shell 10 ga primary & secondary heads | 1,900 |
| 2,000 | 64" x 12'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 3,383 |
| 3,000 | 72" x 15'-0" | 3/16" primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 6,122 |
| 4,000 | 72" x 19'-0" | 3/16" primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 7,024 |
| 5,000 | 96" x 13'-4" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 8,256 |
| 6,000 | 96" x 16'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 9,428 |
| 8,000 | 120" x 14'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 10,750 |
| 10,000 | 10'-6" x 16'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 12,400 |
| 12,000 | 10'-6" x 18'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 14,100 |
| 15,000 | 10'-6" x 24'-0" | 7 ga primary shell / 10 ga secondary shell 1/4" primary & secondary bottom heads / 3/16" roof | 16,250 |
| 20,000 | 10'-6" x 31'-0" | lower 7'-0" primary shell is 1/4", balance of primary shell is 3/16", lower 7'-0" of secondary shell is 3/16", balance of secondary shell is 10 gauge, 1/4" primary & secondary bottom heads, 3/16" roof | 20,165 |
Note Regarding Maximum Allowable Double-Wall Capacity In Your Area